Programming |
|
STARTUP
1. Connect and wire sensor. loads, and power (120 Volt)
2. Energize power, System will read. DAY LIGHT (v2.5)
This will timeout to: SENSE XXX XX (default)
3. Program Hidden Programs (see below)
4. Program Standard Programs (see below)
Note: select SIMULATE for testing, spped up any timers
5. Verify the system goes to default ( SENSE XXX XX)
SYSTEM DEFAULT: "SENSE XXX (sensor reading) ~ XX
(demand reading)
Button operations:
ENTER: Used to access setings (moves right to left)
FUNCTION: Used to scroll through programs
DOWN: Used to raise times, settings, counts, etc.
UP; Used to lower times, settings, counts, etc.
STANDARD PROGRAMS:
(Use FUNCTION button to scroll through the following)
SET LEVEL ON/OFF:
Use UP or DOWN button to scroll through levels
Use ENTER button to set "on" limit
Use ENTER button to set "off' limit
Use UP or DOWN to raise or lower limits
(Repeat for all levels)
SET LEVEL HID TIMER:
Use ENTER button to access on delay
Use UP or DOWN button to increase or decrease timer
(Repeat for all levels)
SET LEVEL CLOUD ON DELAY/OFF DELAY:
Use ENTER button to set "on" delay limit
Use ENTER button to set "off"' delay limit
Use UP or DOWN button to raise or lower delay time
(Repeat for all levels)
|
|
SET
LEVEL OVERIDE TIMER AND FLICKER TIMER:
Use ENTER button to set override timer (0-120 minutes)
Use ENTER button to select flicker time (0-5 minutes)
(0 equals no flicker)
Use UP or DOWN button to raise or lower times
(Repeat for all levels)
SET NORMAL OR SIMULATE:
Use UP or DOWN button to select either normal or simulate
"Normal" is standard default of system
"Simulate" is for testing settings (time delays
are reduced by 10)
Simulate mode will time out after 30 minutes to normal.
HIDDEN PROGAM: (Operate both ENTER and
DOWN button to access)
SET TYPE OF CONTROL:
Use ENTER button then UP or DOWN button to select the
following:
"OFF" will turn off
that level
"TUNNEL" is for reverse
tunnel operation
"DAYLIGHT" is normal
daylighting controls
(Repeat for all levels)
SET SENSOR LIMITS:
Use ENTER button to select desired sensor limit (50O,
1K, 5K, 10K)
SET DEMAND SHED LIMITS:
Use ENTER button to select pulses per second (demand alarm)
(Use UP or DOWN ~~Hon to raise or lower pulse count)
Use ENTER button to set time limits and demand
(Use UP or DOWN button to raise or lower limits)
(Repeat for all levels)
SET TYPE OF OUTPUT:
Use ENTER button to set the board for either two level
or pulsed
(Use UP or DOWN button to toggle between two level or
pulsed)
(Repeat for each board)
SET NUMBER OF LEVELS:
Use UP or DOWN button to set panel levels (1 through 8)
SET CALIBRATIONS:
Set room reading by plugging in portable sensor then press
ENTER
Set permanent sensor by plugging in sensor then press
ENTER
(This will scale the permanent sensor to the area being
controlled)
(For no scale press ENTER twice)
Notes, SIMULATE mode will time out after 30 minutes.
All programs will time out if left unattended.
Levels set to "TUNNEL" mode will operate in
reverse.
Normal settings for a typical should be set to "DAYLIGHT"
For techinal assistance please contact David Long at (206)